DOP-300
DOP-300S is the Delta operator panel (HMI) for machines that have to be not only controlled but also monitored remotely: a 7″ or 10.1″ screen with 1024 × 600 resolution, an ARM Cortex-A7 1.2 GHz dual-core processor, two isolated Ethernet ports, three serial ports and a built-in licence for the DIACloud cloud. The panel collects data from PLCs, AC drives and servos, passes it to MES, SCADA and the cloud via OPC UA and MQTT and gives remote access to the screen and to the PLC program.
Main characteristics
- 7″ (DOP-3S07S3E2) or 10.1″ (DOP-3S10S3E2) screen, 24-bit TFT, 1024 × 600, 400 cd/m²
- ARM Cortex-A7 Dual Core 1.2 GHz, Flash 512 MB, RAM 512 MB
- 2 × Ethernet 10/100 Mbps (isolated, two separate networks), COM1 RS-232, COM2 RS-232/485, COM3 RS-422/485
- USB Type-A, USB Type-C and Micro SD
- OPC UA client and server, MQTT (AWS, Azure, Aliyun), BACnet, Modbus, over 200 PLC drivers
- DIACloud: remote screen (VNC), dashboards, alarms, tunnel to the PLC
- Front IP66 / NEMA 4 / UL Type 4X, operating temperature 0…50 °C, 24 V DC supply
- Programmed with DIAScreen (Windows 8/10/11) — DOP-300 catalogue, 03.2025, and DOP catalogue, 06.2026
or: +359 32 395 989 · sales@mechatronics.bg
Price, availability and lead time on request — for companies and individuals.
DOP-300S — features
- OT and IT in one panel. Machine data (PLCs, AC drives and servos on the serial ports and Ethernet) goes to MES, SCADA, a database and the cloud — via OPC UA with encryption and via MQTT with encrypted transfer.
- Two separate Ethernet networks. The machine and the PC on LAN1 with a static address, the plant network or the internet router on LAN2 — without mixing the addresses.
- Built-in DIACloud licence. The code is on the label on the back: the panel is bound to the account from a phone (QR code and PIN) and needs no separate router for remote access. The first year and 12 GB of traffic are included.
- Dashboards in the browser and on the phone, designed with DIAWebDesigner; the eDIACloud app (Android and iOS) shows the screen, the data, the history and the alarms.
- Notifications via LINE, WeChat, WhatsApp and IFTTT; FTP, Web API, network printer.
- Reports and traceability — batch reports and report management according to FDA 21 CFR Part 11 (pharmaceuticals, food and beverage).
- VNC server and VNC Viewer — the panel can be monitored remotely and can itself display the screen of another panel; RFID operator login, PDF reader, alarms on a Gantt chart.
- Cybersecurity — the specification lists ISO 27001, ISO 27701 and IEC 62443.

Technical data
| Parameter | DOP-3S07S3E2 | DOP-3S10S3E2 |
|---|---|---|
| Screen | 7" TFT LCD, 24 bit | 10.1" TFT LCD, 24 bit |
| Active area | 154.21 × 85.92 mm | 222.72 × 125.28 mm |
| Resolution, backlight | 1024 × 600; LED, half-life > 20,000 h; 400 cd/m² | |
| Touchscreen | 4-wire resistive | |
| Processor, memory | ARM Cortex-A7 Dual Core 1.2 GHz; Flash 512 MB; RAM 512 MB | |
| Ethernet | 2 × 10/100 Mbps, auto-detection, isolated | |
| Serial ports | COM1 RS-232 (with flow control); COM2 RS-232/RS-485; COM3 RS-422/RS-485 | |
| USB, card | USB Type-A 5 V / 1000 mA; USB Type-C 5 V / 500 mA (host); Micro SD | |
| Buzzer | 2–4 kHz / 80 dB | |
| Power supply | 24 V DC −15…+15 %, from an isolated source (Class 2 / SELV); withstand test 500 V AC for 1 min | |
| Power consumption | up to 14.7 W | up to 16.2 W |
| Clock battery | CR2032, approx. 3 years | |
| Front protection | IP66 / NEMA 4 / UL Type 4X (indoor) | |
| Environment | operation 0…50 °C; storage −20…60 °C; 10–90 % RH at 0–40 °C, 10–55 % RH at 41–50 °C; pollution degree 2 | |
| Vibration, shock | according to IEC 61131-2; IEC 60068-2-27 — 15 G, 11 ms | |
| Dimensions (W × H × D) | 196 × 136 × 39 mm | 270 × 180.9 × 47.25 mm |
| Panel cut-out | 186.8 × 126.8 mm | 255 × 170 mm |
| Weight | approx. 880 g | approx. 940 g |
| Certificates | CE, UL | |
Source: Delta DOP-300 catalogue, 03.2025, p. 14; the dimensions on the drawing in the DOP catalogue of 06.2026, p. 42, are 196.5 × 136.5 and 270.5 × 181.4 mm (with the bezel). Cooling — natural; built-in clock.
Interfaces

Wireless connection: LTE in bands B1/B3/B5/B7/B8/B20/B38/B40/B41 and Wi-Fi 2.4 GHz 802.11 b/g/n — for its full functionality Delta recommends its own wireless module (DOP catalogue, 06.2026, p. 16).
Communication and protocols
| Group | Supported |
|---|---|
| OPC UA | client and server, encryption |
| MQTT | client (publish and subscribe) and broker; AWS, Azure, Aliyun |
| BACnet | MS/TP, BACnet UDP, BACnet/IP server |
| Modbus | 984 RTU and ASCII (master and slave), TCP/IP |
| Delta and other PLCs | over 200 drivers — Delta AS, DVP, Siemens (incl. MPI), Mitsubishi, Omron, Allen-Bradley, Beckhoff and others; CODESYS; Digital Memory Link |
| IT services | Web monitoring, Web API, FTP, e-mail, network printer, database |
Source: DOP catalogue, 06.2026, pp. 12–13 and 37.
Remote access via DIACloud
The panel connects to DIACloud by cable (LAN2 to a router with internet) or via the DX-MWB-01N Wi-Fi/4G dongle and is bound to the account from the eDIACloud app. Then the panel screen (VNC), the dashboards and the alarms open in the browser or on the phone, and DIACom creates a tunnel to the PLC for uploading the program and online monitoring.
Step by step (in Bulgarian): DOP-300 applications and remote access setup →

Accessories and subscriptions
| Code | Description | Note |
|---|---|---|
| DX-MWB-01N | wireless module Wi-Fi 2.4 GHz 802.11 b/g/n, WPA/WPA2, 0…50 °C | for DOP-3S07S3E2 and DOP-3S10S3E2; CE |
| DX-TCA-0500 | Cloud Application card — 500 TAGs for 1 year | data analysis and visualisation in DIACloud |
| DX-TRA-0036 | Remote Access card — 36 GB for 1 year | VNC and PLC program upload/download |
| DX-TRA-9912 | Remote Access card — 12 GB | DOP-300 and DOP-100 (wireless network only) |
| DIAScreen | screen design software | Windows 8/10/11, 32/64 bit |
| DIAWebDesigner | software for the DIACloud dashboards and reports | Windows 8/10/11, 32/64 bit |
The cards are activated within two years of delivery from Delta and are valid for one year after activation. On registration the account receives 20 TAGs and 1 template free of charge for 1 year. Source: DOP catalogue, 06.2026, p. 58; DIACloud manual, 10.2025, pp. 35 and 42.
Applications
- monitoring of compressors and compressor stations;
- pumping stations and pressure boosting systems;
- medical equipment and pharmaceuticals — reports according to FDA 21 CFR Part 11;
- food and beverage production — batch traceability;
- building automation — BACnet;
- machines that the manufacturer services remotely.
Source: DOP catalogue, 06.2026, p. 18.
Product documents